34
DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
8. Connecting the furnace
8.4.2 Lengths of the air/flue gas pipes
Lmax is measured by adding the lengths of the air/flue gas
pipes and the equivalent lengths of the other elements.
(x) For Germany only
Take the pressure drops into account if using accessories
(elbows, inspection pipe, etc.).
8.4.3 Connection options
Z
Refer to the current price list.
Type of air/flue gas connection Diameter
Maximum length of the connection pipes (metre)
DTGE130-35 DTG130-35 DTG130-45 DTG130-65 DTG130-90 DTG130-115
Concentric pipes connected to
a horizontal terminal (Alu)
C
13(x)
80/125mm161616 - - -
100/150 mm - - - 9 8 5.9
Concentric pipes connected to
a vertical terminal (Alu)
C
33(x)
80/125 mm 14.5 14.5 14.5 - - -
100/150 mm - - - 11.5 10 9.4
Concentric pipes in the boiler
room
Single pipes in the chimney
(combustive air in counter
current) (Alu)
C
93(x)
80/125 mm
80 mm
15 15 15 - - -
80/125 mm
110 mm
11.5 11.5 25 - - -
110/150 mm
110 mm
- - - 16 13.2 10
Concentric pipes in the boiler
room
"Flex" pipes in the chimney
(combustive air in counter
current) (PPS)
C
93(x)
80/125 mm
80 mm
12 12 12 - - -
110/150 mm
110 mm
- - - 16.5 13.5 9.4
Bi-flow adapter + Separate
single air/flue gas pipes
(combustive air taken from
outside) (Alu)
C
53
80/125 mm on
2x80 mm
20.5 20.5 20.5 - - -
100/150 mm on
2x100 mm
- - - 23 17.5
Air: 11
flue gases: 5
Chimney (rigid or flexible)
(combustive air taken in the
premises) (PPS)
B
23P
80 mm (rigid) 23.5 23.5 23.5 - - -
110 mm (rigid) - - - 40 40 40
80 mm (Flexible) 21 21 21 - - -
110 mm (Flexible) - - - 29.5 24 17.5