DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
10. Messages - Alarms
10 Messages - Alarms
10.1 Faults
In the event of a fault, the display may show the following messages. Contact your fitter.
Message Probable causes Action
SHOW REM. CTRL
The message SHOW REM.CTRL
indicates the presence of an override on
a remote control
To cancel the overrides on all remote controls, press the AUTO key for 5 seconds.
REVISION Boiler service required
Contact the professional responsible for maintenance of the boiler.
24V SHORT-CIRC. Short circuit 24 V Check the wiring.
Faults Probable causes Action
BURNER FAILURE Igniter fault Check the ignition electrode (spacing of the electrodes), its connector and its connection
cable
. Replace if necessary.
Ionization fault
Check the earth
. Check the ionization current. If necessary rectify the level of CO
2
.
Gas valve defective
Replace the gas valve
.
No gas or presence of air in the pipe
Measure the gas supply pressure
. Bleed the gas circuit.
I-CURRENT FAIL Ionization fault during operation
Check the earth
. Check the ionization current. If necessary rectify the level of CO
2
.
MCBA FAILURE XX Internal safety control box fault
Reset the boiler
. Briefly cut the electrical power supply to the boiler using the On/Off
switch
. Replace the command and safety box.
MCBA FAILURE 5 External influences
Check the wiring
.
MCBA FAILURE 11 Internal fault
Check that multi-wire connections are undamaged
. Presence of humidity in the control
panel
. Eliminate electro-magnetic influences.
DEF.MCBA 24 Boiler reversal sensor and return sensor
Reverse the sensors
. Pump incorrectly fitted.
VALVE FAIL Combined gas valve unit defective
The safety control box does not signal a gas valve
. Check:
- The wiring of the gas valve;
- The gas valve could be defective (coil defective).
REARM CVI Control error
Reset the boiler
.
MCBA.COM.FAULT Communication error between
DIEMATIC and safety control box
Check the link and the connections between DIEMATIC and safety control box
. Reset
the boiler
. Briefly cut the electrical power supply to the boiler using the On/Off switch.
BOILER S.FAIL.
BACK S.FAILURE
OUTSI. S.FAIL.
DHW S. FAILURE
OUTL S.B FAIL.
OUTL S.C FAIL.
ROOM S.A FAIL.
ROOM S.B FAIL.
ROOM S.C FAIL.
SMOKE S. FAIL.
SWIM.P. S.FAIL
ST.TANK S.FAIL
The corresponding sensor is off or
short-circuited
Check the link and the connectors
. Replace the sensor if necessary.