15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
11. "User" settings
11.3 Adjustment
*The line or title is only displayed for the options, circuits or
sensors actually connected.
At the end of the intervention, the data is memorised after 2
minutes or by pressing the AUTO key.
Press Display Parameter set Factory setting
Adjustment
range
Customer setting
J
then
I
#SETTING The parameters are set using keys
or
.
CONTRAST DISP. Allows the display contrast to be set using keys
and
BACK LIGHT ON Lighting is permanent if the circuit is on comfort
period. If the circuit displayed is in a reduced
period, the light shows ECO
.
ON
ON, ECO or
OFF
ECO The lighting stays on for 2 minutes if you press a
key on the keyboard.
OFF The display is never lit
PERMUT * AUTO Used to change the activation order of the
cascade every 7 days.
AUTO AUTO, 1, 2, ...10
1, 2,
. . . 10
Imposes the cascade's master boiler.
SUM/WIN Non heating exterior temperature
22 °C
15 to 30 °C,
OFF
CALIBR. OUT Outside sensor calibration 0.0 -5.0 to +5.0 °C
CALIBR. ROOM A * Calibration of the room sensor on circuit A 0.0 -5.0 to +5.0 °C
OFFSET ROOM A * Room offset on circuit A
(If no room sensor is connected)
0.0 -5.0 to +5.0 °C
ANTIFR. ROOM A * Room temperature antifreeze activation on
circuit A
6 °C 0.5 to 20 °C
CALIBR. ROOM B * Lines as circuit A 0.0 -5.0 to +5.0 °C
OFFSET ROOM B * Lines as circuit A 0.0 -5.0 to +5.0 °C
ANTIFR. ROOM B * Lines as circuit A 6 °C 0.5 to 20 °C
CALIBR. ROOM C * Lines as circuit A 0.0 -5.0 to +5.0 °C
OFFSET ROOM C * Lines as circuit A 0.0 -5.0 to +5.0 °C
ANTIFR. ROOM C * Lines as circuit A 6 °C 0.5 to 20 °C