DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
11. "User" settings
` SUM/WIN
Used to set the outside temperature above which heating will be
shut down.
- The heating pumps are shut down,
- The burner will only start for domestic hot water needs,
- The symbol
E
appears.
If this parameter is set to NO, heating will never be shut down
automatically.
` CALIBR. OUT: Outside sensor calibration
Used to correct the outside temperature.
For example: Actual outside temperature = 10°C
Temperature displayed = 11°C: Set CALIBR. OUT to -1.
• CALIBR. ROOM...: Room calibration
(With room sensor)
Used to correct the room temperature.
For example: Set temperature = 20°C
Temperature displayed = 19°C: Set the CALIBR. OUT to +1
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
` AMB OFFSET...: Room offset
(Without room sensor)
Is used to set a room offset.
For example: Set temperature = 20°C
Measured temperature = 19°C: Set OFFSET ROOM to +1.
Make this setting 2 hours after switching on, when the room
temperature has stabilised.
` ANTIFR. ROOM...: Room antifreeze
(With room sensor)
Used to set the room temperature maintained in antifreeze mode
for each circuit.