DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
9. Commissioning
9.3.2 DTG130-115
For Belgium: Any work on the gas block must be carried
out by a factory technician (For example: SERV’élite).
The boiler is preset in the factory to operate on natural gas G20 G20.
The conversion from Natural Gas G20 to Natural Gas G25 requires
the installation of the conversion kit delivered with the boiler.
Maximum power of the burner (Factory setting in kW)
The burner is set exclusively by checking the CO
2
or O
2
level in the
flue gases at minimum output.
Compare the information on the appliance's rating plate with the type
of gas available in situ.
- If natural gas G20 is being used, this boiler can be commissioned
without making any other preliminary settings,
- If natural gas G25 is being used, the G25 conversion kit must be
fitted (diaphragm diameter 9.8) between the gas valve and the
venturi,
- If propane G31 is being used, the propane injector kit must be
installed (gas valve + diaphragm diameter 6.7)
Z
See: Conversion kit instructions.
Fitting the G25 natural gas conversion kit
Replace the diaphragm diameter 8.6 with the diaphragm diameter
9.8 in the sachet.
Boilers DTG130-115
Heating mode (100 %) (Hi / Hs) 110.2 / 122.3
Domestic hot water mode (100%) (Hi / Hs) 110.2 / 122.3