9. Commissioning
` Set the burner output to minimum using the - key.
: Minimum
output.
` Measure the CO
2
or O
2
level in the flue gases.
` If necessary:
Modify the "min output" setting with the setting screw
(The
adjustment screw is protected by a plug, Torx type screw and
plug).
Turn the screw clockwise to increase the CO
2
and anti-
clockwise to decrease the O
2
Correct the burner setting to ±0.1% CO
2
; ±0.2% O
2
.
` Check the CO
2
and O
2
content again at maximum output.
For Switzerland
: The maximum limit values authorised by the
OPAIR federal order on air protection regarding CO and NOx must
be checked using measurements made in the place of installation.
When the setting is correct, close the flap.
` Switch the On/Off switch on Off.
` Remove the measuring equipment.
` Replace the plastic plug onto the measuring tube.
CO
2
content
(%)
O
2
content
(%)
Natural gas G20 9.5 3.9
Natural gas G25 9.5 3.9
Propane 10.5 4.9