15/02/2011 - 300014279-001-J DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus
12. Installer settings
12.4 Parameter and input/output check (mode tests)
* The line or title is only displayed for the options, circuits or
sensors actually connected.
** The line is only displayed for boiler 1.
Press Display Output or input parameter status
K
10 seconds then
I
#PARAMETERS
PERMUT Cascade permutation status (1 = permutation 1-2, 2 = permutation 2-1)
STAGE Current speed (Number of boilers requesting heating)
NB.CASC.: Number of boilers recognised in the cascade
POWER % Temporary output % (0 % = Minimum output or burner off)
SPEED B.(RPM) Fan speed (Measured values)
CONS.RPM Instruction set fan rpm
MEAN OUTSIDE T Average outside temperature
CALC.T. BOILER Temperature calculated by the boiler
BOILER. T. Measured boiler temperature
CALC.T.CASC** Calculated temperature cascade outlet
CASCADE TEMP.** Measured temperature cascade outlet
CALCULATED T. A Calculated temperature for circuit A
CALCULATED T. B* Calculated temperature for circuit B
OUTLET TEMP. B Measured start temperature B
CALCULATED T. C* Calculated temperature for circuit C
OUTLET TEMP. C Measured start temperature C
KNOB A* Position of temperature setting button on room sensor A
KNOB B* Position of temperature setting button on room sensor B
KNOB C* Position of temperature setting button on room sensor C
OFFSET ADAP A* Parallel trigger calculated for circuit A
OFFSET ADAP B* Parallel trigger calculated for circuit B
OFFSET ADAP C* Parallel trigger calculated for circuit C
J
then
I
#DEF. HISTORY Failure history
1 FAIL... Failure memorised + day, month and time of the failure
...
10 FAIL... Failure memorised + day, month and time of the failure
J
then
I
#TEST OUTPUTS
BURNER : YES/NO Stop/start burner
AUX.CIR.P : YES/NO On/Off auxiliary outlet
DHW PUMP : YES/NO* Stop/start domestic hot water pump
P.CIRC.A : YES/NO Stop/start pump circuit A
OP. 3WVB: YES/NO* Open/Close valve circuit B
CLOSE V3WB: YES/NO* Close/Stop valve circuit C
P.CIRC B : YES/NO* Stop/start pump circuit B
OPEN 3WV C: YES/NO* Open/Close valve circuit C
CLOSE V3W C: YES/NO* Close/Stop valve circuit C
P.CIRC. C: YES/NO* Stop/start pump circuit C