DTG(E)130 - 35/45/65/90/115 Eco.NOxPlus 15/02/2011 - 300014279-001-J
12. Installer settings
12.3 Miscellaneous
* The line or title is only displayed for the options, circuits or
sensors actually connected.
At the end of the intervention, the data is stored after 2 minutes
or by closing the flap.
` BAND WIDTH
Option of increasing the bandwidth if the valves are rapid or of
reducing it if they are slow.
` H. PUMP DELAY
The timing of heating pump shutdown prevents the boiler
overheating.
` HW. PUMP DELAY
The timing of the domestic hot water load pump shutdown prevents
the boiler and the heating circuits overheating.
` LEG PROTEC
The domestic hot water tank is overheated to 70º C every Saturday
from 4 to 5 o'clock. The anti-legionnaires function prevents the
appearance of legionella in the tank.
Set the maximum temperature of the boiler (BOILER MAX.) to
80°C and fit a mixing system which prevents the distribution of
domestic hot water at a temperature higher than 60°C.
Press Display Parameter set Factory setting
Adjustment
range
Customer
setting
J
then
I
#MISCELLANEOUS The parameters are set using keys
or
DSP ALTERNATED Alternate display of the two preceding displays
ALTERNATED
ALTERNATED
TIME - DAY
BOILER. T.
TIME - DAY Permanent time display
BOILER. T. Permanent temperature display
BAND WIDTH Control unit bandwidth for the 3-way valves 12 K 4 to 16 K
BOIL/3WV SHIFT* Minimum temperature difference between the
boiler and the valves
4K 0 to 16K
H. PUMP DELAY Timing of the shutdown of the heating pumps
4 minutes
0 to
15 minutes
HW. PUMP DELAY* Timing of the shutdown of the domestic hot water
pump
2 minutes
0 to
15 minutes
ADAPT* ON Automatic adaptation of the heating curves for
each circuit with a room sensor with an influence
of > 0
ON ON or OFF
OFF The heating curves can only be modified
manually
DHW * TOTAL Interruption of pool heating and reheating during
domestic hot water production
TOTAL
TOTAL
SLIDING
NO PRIOR.
SLIDING Domestic hot water production and valve circuit
heating if available output is sufficient
NO PRIOR.
Heating and domestic hot water production
.
Risk of overheating in the direct circuit.
LEG PROTEC* Activation of the leg protec function OFF OFF or ON
BURN.MIN.RUN Setting the burner minimum operation time 1 minute 0 to 4 minutes
B.P. DELAY* Timing of the boiler pump shutdown if using a
cascade
3 minutes
1 to
30 minutes